Shiva Amvaj logo
  • Product Name
  • Specifications
  • Related Products
  • Product Reviews

Three-Phase ProtectorLoad Controller

The Shiva Amvaj Digital Load Controller (FN Series) provides dependable monitoring against current asymmetry, undercurrent, and overcurrent in industrial applications.

Designed in two models: 1-100A (1A accuracy) and 0.5-30A (0.1A accuracy).

Product Models

DLFN-30Aکنترل بار دیجیتال 30 آمپر سری FN
DLFN-100Aکنترل بار دیجیتال 100 آمپر سری FN
3-Year Replacement Warranty
3-Year Replacement Warranty
Product Specifications

Code:

13FN1

Weight:

200 gr

Dimensions:

65*62*95 mm

IP:

30

Supply Voltage:

180-250VAC /50-60 HZ

Operating Conditions:

دما: ۶۵+..۲۰– درجه سانتی گراد و رطوبت : ۷۰درصد

Output:

رله 5A

Specifications of DLFN-30A کنترل بار دیجیتال 30 آمپر سری FN

Current Display Accuracy:

0.1A

Specifications of DLFN-100A کنترل بار دیجیتال 100 آمپر سری FN

Current Display Accuracy:

1A

Features of the Shiva Amvaj Digital Load Controller (FN Series)

  • Current control based on the I2t curve

  • Current measurement without CT, with direct cable passage up to 25mm²

  • Display of current, set values and error messages

  • Protection against over-current, under-current and current asymmetry

  • Unlimited reset setting capability

  • Two operating modes, manual and automatic, for current control at initial start-up

  • 8 indicators to signal

    • OL: Over-current (1-100A) , (0.1-30A)

    • UL: Under-current adjustable from zero to 1 unit below (OL)¹

    • A%: Current asymmetry (7-100% )

    • ON: Turn-on delay (0-240Sec)

    • OFF: Trip delay for OL and A% errors (0-20Sec)

    • (u)OFF: Trip delay for UL error ( 5-10Sec)

    • Normal: Relay status

    • Delay Start: Initial start time

      • Manual mode (0-120Sec)

      • Automatic mode (5Sec)

(Indicators are steady in setting state and blink in error state)

1. If UL is set to zero, under-current protection is disabled.


Device operation

The FN series digital load controller has two operating modes, which are selected in the settings section:

1. Manual mode (Han): With this mode selected, over-current is not controlled during the initial start time, which can be between ( 0-120Sec).

2. Automatic mode (Aut): In this mode, to prevent motor jamming, over-current is controlled during the initial start time, which is 5 seconds. If the current meets one of the 3 conditions below, the device detects the fault, the relay trips immediately, and the display shows the blinking text HHH:

The passing current is more than twice the device CT value: 60A model:DLFN-30A and 200A model:DLFN-100A

The current is more than 3 times the set maximum current (OL).

The current is above the set maximum current (OL) and continues for 5 seconds, even if it is decreasing, i.e. still above the set maximum current after 5 seconds.

Note: In both operating modes, during the initial start time the display shows the passing current for 2 seconds and the Delay Start countdown for 2 seconds.

Shiva Amvaj logoShiva Amvaj

Shiva Amvaj Asia Company was established in 1988 in Isfahan, Iran. The company specializes in the design and manufacture of industrial electrical equipment and various types of relays used in the electrical industry. Producing custom-designed equipment for companies and industrial factories, with reliable quality and an official 3-year warranty, is one of our core commitments.

Company Address: Isfahan, Jey Industrial Town, End of Fourth Street, No. 111