Three-Phase ProtectorPhase & Load Monitoring Relay
The Shiva Amvaj Phase & Load Controller (FN Series) features upgraded hardware and software to reliably detect and protect against phase loss, phase sequence reversal, voltage and current asymmetry, over/undervoltage, and over/undercurrent in industrial facilities.
Available in two models: 1-100A (1A resolution) and 0.5-30A (0.1A resolution).
Product Models

Code:
13FN2
Weight:
210 gr
Dimensions:
65*62*95 mm
IP:
30
Supply Voltage:
180-250VAC/ R-N /50-60 HZ
Input Voltage:
300-500VAC/3PH/50-60Hz
Operating Conditions:
دما: ۶۵+..۲۰– درجه سانتی گراد و رطوبت : ۷۰درصد
Output:
رله 5A
Current Display Accuracy:
0.1A
Current Display Accuracy:
1A
Features of the Shiva Amvaj Load Phase Controller (FN Series)
Current control based on the I2t curve
Current measurement without CT, with direct cable passage (maximum 25mm²)
Display of current, set values and error messages
Protection against
Over-current, under-current and current asymmetry
Over-voltage, under-voltage and voltage asymmetry, phase loss and phase sequence error
Voltage display capability
Two operating modes, manual and automatic, for current control at initial start-up
10 indicators to signal
OL: Over-current ( 1-100A ),( 0.1-30A )
UL: Under-current ( adjustable down to 1 unit below OL)¹
A%: Current asymmetry ( 7-100% )
OV: Over-voltage ( 400-480V )
UV: Under-voltage ( 310-380V )
V%: Voltage asymmetry ( 7-25% )
OFF: Trip delay ( current error A 0-20 Sec )
OFF: Trip delay ( voltage error U 0-10 Sec )
Normal: Relay status( blinking: ready for Reset)
On Delay: Turn-on delay ( 0-240Sec )
Delay Start: Initial start time
Manual mode ( 0-120Sec )
Automatic mode (5Sec)
(Indicators are steady in setting state and blink in error state)
1. One unit equals 0.1A in the 30A model and 1A in the 100A model. If UL is set to zero, under-current protection is disabled.
Device operation
The FN series load phase controller has two operating modes, which are selected in the settings section:
1. Manual mode (Han): With this mode selected, over-current and under-voltage are not controlled during the initial start time, which can be between ( 0-120Sec).
2. Automatic mode (Aut): In this mode, to prevent motor jamming, over-current and under-voltage are controlled during the initial start time, which is 5 seconds. If the current meets one of the 3 conditions below, the device detects the fault, the relay trips immediately, and the display shows the blinking text HHH:
The passing current is more than twice the device CT value: 60A model:LPFN-30A and 200A model:LPFN-100A
The current is more than 3 times the set maximum current (OL).
The current is above the set maximum current (OL) and continues for 5 seconds, even if it is decreasing, i.e. still above the set maximum current after 5 seconds.
Note: In both operating modes, during the initial start time the display shows the passing current for 2 seconds and the Delay Start countdown for 2 seconds.